Standard and option features
Technical Data
| |
Sunsys
HPS
40 |
Sunsys
HPS
60 |
Sunsys
HPS
80 |
Sunsys
HPS
100 |
Sunsys
HPS
120 |
Sunsys
HPS
160 |
Sunsys
HPS
200 |
| AC output nominal power |
40 kVA |
60 kVA |
80 kVA |
100 kVA |
120 kVA |
160 kVA |
200 kVA |
| AC active power |
32 kW |
48 kW |
64 kW |
80 kW |
100 kW |
128 kW |
160 kW |
| AC output voltage |
380 / 400 / 415 VAC adjustable / 3 phases + Neutral (± 1%) |
| AC output frequency |
50 / 60 Hz adjustable (± 0.2 Hz) |
| THDV |
< 2 % |
| Crest factor |
3:1 |
| Overload |
125 % for 10 min / 150 % for 1 min |
| Max voltage of the PV production |
900 VDC |
| MPPT(1)voltage range of the PV production |
480 to 900 VDC |
| Max photovoltaic power(2) |
30 kWp |
80 kWp |
160 kWp |
240 kWp |
| Efficiency |
94 % |
| Battery configuration |
180 cells |
| Battery type |
Cyclic sealed lead or open vent |
| Grid / Genset voltage |
380 / 400 / 415 VAC / 3 phases + Neutral (± 15%) |
| Grid / Genset frequency |
50 / 60 Hz (± 5 Hz) |
| Operational temperature |
0 °C to 40 °C depending on the model (25 °C for maximum battery life) |
| Degree of protection |
IP20 |
| Dimensions W x D x H |
1800 x 845 x 1930 mm |
2400 x 845 x 1930 mm |
3200 x 845 x 1930 mm |
| Weight |
990 kg |
1460 kg |
1540 kg |
1840 kg |
|
(1) Maximum Power Point Tracking.
(2) Different power outputs are available.