UPS SOCOMEC MODULYS EM

UPS SOCOMEC MODULYS EM

from 3 to 6 kVA single-phase

A centralised power supply for your emergency systems

Centralised power supply systems are designed for buildings subject to fire safety regulations They comply with EN 50171.

The CPSS are designed chiefly to supply emergency lighting in the event of a failure in the normal power supply, but can also be used to supply other emergency systems, for example:

automatic fire extinguishing installations,

emergency detection and warning units,

smoke extraction equipment,

carbon monoxide detection systems,

specific safety installations in sensitive areas.

Complies with standards

The EMergency EM range has been developed in compliance with European standards. The product is defined as a "Central Supply System" running on AC current under 1000 V and employing batteries as a backup power source

Using a centralised power supply system

reduces installation costs

simplifies mandatory periodic test operations

eliminates the drawbacks caused by thermal stress on back-up batteries located in high places

reduces the cost of your investment

reduces operational costs (long-term reliability).

Emergency : improved RELIABILITY

The battery is a vital part of Backup Power Supply systems.

Advantages

Centralised power source EN 50171

On line double conversion technology (VFI-SS-111)

Precise voltage and frequency

Fully digital controls

Integrated batteries (up to 60 minutes)

High capacity batteries with a 10 year life

Batteries tested automatically

Monitoring and control panel with alphanumeric display

Serial RS 232 interface

Serial RS 485 interface for 4.5 and 6 kVA models

Dry contacts interface.

Operating modes

Changeover mode

Mode without interruption

Changeover mode with additional control switching device for central and partial switching of the load (on request)

Non-maintained changeover mode

Accessories (on request)

Galvanic isolation transformer

Permanent isolation controller

Standard and option features
Technical Data
Model Input/output kVA  kW Dimensions (WxDxH) mm Weight (kg)
 MOD EM 130 1/1 3 2.1  444x795x1000  240
MOD EM 145 1/1 4.5 3.15  444x795x1000  330
MOD EM 160 1/1 6 4.2 444x795x1000  340
Rectifier input
Voltage single-phase 230 V (1ph+N) ± 20 %
Permissible tolerance up to -30 % at 70% nominal load
Frequency 50 - 60 Hz ± 10 %
Absorbed current THDI < 5 %
Power factor upstream > 0.98
Output
Voltage single-phase 230 V
Tolerance under static conditions ± 3 %
Frequency (configurable) 50 - 60 Hz
Frequency tolerance ± 0.1 %
Admissible crest factor without de-rating 3:1
Back-up time 60 min1
Overload 130 %
Environment
IP rating (IEC 60529) IP 20
Noise level  (ISO3746) < 52 dBA at 1 metre
Compliant with:
Centralised power supply system EN 50171
Reference standards EN / IEC 62040-1 safety
EN 50091-2 EMC
IEC 62040-3 performance
Classification (IEC62040-3) UPS VFI2 - SS - 111

(1) Other back-up times on request

(2) Voltage Frequency Independent