UPS SOCOMEC MASTERYS IP+ RAIL CMI
Standard and option features
Standard electrical features
Dual input mains.
Internal maintanance bypass.
Backfeed protection: detection circuit.
EBS (Expert Battery System) for battery management.
Electrical options
- Long-life batteries.
- External battery cabinet (degree of protection up to IP32).
- External temperature sensor.
- Additional battery chargers.
- Additional transformer.
- Parallel kit.
- Cold start.
- ACS synchronization system.
- Neutral creation kit for mains without neutral.
- Tropicalization and anti-corrosion protection for electrical boards.
Standard communication features
- Multilanguage graphic display.
- Dry-contact interface.
- MODBUS/JBUS RTU.
- Embedded LAN interface (web pages, email).
- 2 slots for communication options.
Communication options
Technical Data
Energy storage option: ultracapacitor
Ultracapacitor could be a suitable battery replacement in special situations where a long back-up time is not required. This solution is targeted specifically to ride-through frequent voltage dips and short power outages, or simply bridge the startup of a generator, or where ambient temperatures could compromise battery lifetime. This would result in a highly reliable energy storage system that would require no maintenance.
Advantages
- Extremely long lifetime: 15 years with virtually unlimited cycling.
- High-reliability – No maintenance.
- Wide temperature range up to 45 °C
- Ultra rapid charging
- Battery-free, lead-free and environment-friendly
Sn [kVA] |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
Pn [kW] - 3/1 |
9 |
13,5 |
18 |
27 |
32 |
48 |
|
Pn [kW] - 3/3 |
9 |
13,5 |
18 |
27 |
32 |
48 |
64 |
Parallel configuration(1) |
Available up to 6 units for power extension or redundancy |
Efficiency |
Up to 95% in VFI –SS-11 mode TÜV verified (transformer excluded) |
Input |
Rated voltage |
400 V (3ph + N) |
Voltage tolerance |
± 20%(3) (up to -40% @ 50% of rated power) |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 10% |
Power factor / THDI(2) |
0.99 / < 3% |
Output |
Rated voltage |
1ph+n/2ph 230(220/240 configurable)(3)
3ph + N: 400 V (380/415 V configurable) (3) |
Voltage tolerance |
± 1% |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 2% (configurable from 1% to 8% with generator set) |
Total output voltage distortion - linear load |
< 1 % |
Total output voltage distortion - non-linear load |
< 5 % |
Overload |
125% for 10 minutes, 150% for 1 minute |
Crest factor |
3:1 (complying with IEC 62040-3) |
Power factor without derating |
From 0.6 lagging up to 0.9 leading |
Bypass |
Rated voltage |
1ph + N: 230 V, 3ph + N: 400 V |
Voltage tolerance |
± 15% (configurable from 10% to 20% with generator set) |
Rated frequency |
50/60 Hz |
Frequency tolerance |
± 2% (configurable from 1% to 8% with generator set) |
Environment |
Operating ambient temperature |
from 0 °C up to +40 °C (from 15 °C to 25 °C for maximum battery life) |
Relative humidity |
0 % - 95 % without condensation |
Maximum altitude |
1000 m without derating (max. 3000 m) |
Acoustic level at 1 m
(ISO 3746) |
< 52 dBA |
< 55 dBA |
< 65 dBA |
Dimension and weight - UPS single cabinet |
Dimensions (3/1) W x D x H |
600 x 800 x 1400 mm |
1000 x 835 x
1400 mm |
- |
Dimensions (3/3) W x D x H |
600 x 800 x 1400 mm |
1000 x 835 x
1400 mm |
Weight (3/1) |
230 kg |
250 kg |
270 kg |
330 kg |
490 kg |
540 kg |
- |
Weight (3/3) |
230 kg |
250 kg |
270 kg |
320 kg |
370 kg |
500 kg |
550 kg |
Degree of protection |
IP31 and IP52 as option (according to IEC 60529) Coated electronic boards(4) |
Colours |
RAL 7012 |
Standards |
Safety |
EN 62040-1 (TÜV SÜD certified), EN 60950-1, LU 1-085 (Section 12 LU) (4) |
Type and performance |
EN 62040-3 [VFI-SS-111] |
EMC |
EN 62040-2 (2nd Edition) G-222 EN 50121 |
Product declaration |
CE |
(1) With transformer on input/bypass side.
(2) For source THDV < 2 % and nominal load.
(3) Three-phase 220-230-240 V from 15 to 40 kVA.
(4) Section 12 version units on