UPS SOCOMEC MASTERYS GP from 10 to 120 kVA/kW

UPS SOCOMEC MASTERYS GP from 10 to 120 kVA/kW

MASTERYS GP from 10 to 120 kVA/kW

Solutions for your business critical applications

The solution for

Data servers

Telecommunications

Service sector

Advantages

A complete, cost-effective solution

  • Online double conversion mode with an output power factor of 0.9 providing 12% more active power compare to UPS with a power factor of 0.8.
  • Dual input mains allows you to manage independent power sources.
  • Increased system availability placing two UPS in parallel for 1+1 redundancy
  • Internal manual bypass for easy maintenance without power interruption.
  • Internal batteries providing more than 1 hour runtime (MASTERYS BC 15-80 kVA).
  • Multilanguage display.

Tailored to your environment

  • Saves space with a reduced footprint and optimized cabinet size.
  • Low noise level.
  • Flexible battery solutions
  • Compact, lightweight and easy to install
  • Extended battery life and performance with exclusive EBS battery charging management for increased battery life.
Standard and option features

Standard electrical features

Dual input mains.

Internal maintanance bypass.

Backfeed protection: detection circuit.

EBS (Expert Battery System) for battery management.

Electrical options

  • External battery cabinet.
  • External temperature sensor.
  • Additional battery chargers.
  • Galvanic isolation transformer.
  • Parallel kit.
  • ACS synchronization system.

Standard communication features

MODBUS/JBUS RTU.

2 slots for communication options.

Communication options

  • Dry-contact interface.
  • Remote mimic panel.
  • MODBUS TCP.
  • PROFIBUS
  • NET VISION: professional WEB/SNM interface for UPS monitoring and shutdown management of several operating systems.
  • Remote monitoring service

Technical Data

 

Sn [kVA] 15 20
Pn [kW] 13.5 18
Input / output 3/1
Parallel configuration 1+1 (1)
Input
Rated voltage 400 V (3ph + N)
Voltage tolerances 240 V to 480 V(2)
Rated frequency 50/60 Hz ± 10%
Power factor / THDI 0.99 / < 3%
Output
Rated voltage 1ph + N: 230 V (can be configured 220/240 V)
Voltage tolerance  static load ±1% dynamic load in accordance with VFI-SS-111
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable from 1% to 8%)
Overload 125% for 10 minutes, 150% for 1 minute
Crest factor 3:1
Bypass
Rated voltage rated output voltage
Voltage tolerance ± 15% (configurable with from 10% to 20%)
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable for Genset compatibility)
Efficiency
Online mode @ 100 % of load up to 94%
Environment
Operating ambient temperature from 0 °C up to 40(2) °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m
(ISO 3746)
< 52 dBA < 55 dBA
UPS cabinet  
Dimensions W x D x H 444 x 795 x 800  / 1000 / 1400 mm
Weight 105 kg(3) 110 kg(3)
Degree of protection IP20
Colours RAL 7012
Standards
Safety EN 62040-1 (TÜV SÜD certified), EN 60950-1
Performance EN62040-3 (VFI-SS-111)
EMC EN62040-2 
Product declaration CE

(1) The standard model is prepared for a 1+1 redundant system. Upon request, it is possible to have connected up to 6 modules in a parallel system.

(2) Conditions apply.

(3) Without batteries.