UPS SOCOMEC MASTERYS BC (8-12 kVA)
Standard and option features
Standard electrical features
Backfeed protection: detection circuit.
EBS (Expert Battery System) for battery management.
Electrical options
- Dual input mains.
- Internal maintanance bypass.
- External maintanance bypass.
- External battery cabinet.
- Galvanic isolation transformer.
- Parallel kit.
Standard communication features
MODBUS/JBUS RTU.
2 slots for communication options.
Communication options
- Dry-contact interface.
- Remote mimic panel.
- MODBUS TCP.
- PROFIBUS.
- NET VISION: professional WEB/SNM interface for UPS monitoring and shutdown management of several operating systems
Technical Data
UPS and internal batteries
Sn [kVA] |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
Pn [kW] (0 °C ÷ 35 °C) |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
Input / output 3/1 |
• |
• |
• |
|
|
|
|
|
|
Input / output 3/3 |
• |
• |
• |
• |
• |
• |
• |
• |
• |
Parallel configuration |
up to 6 units |
Input |
Rated voltage |
400V 3ph + N |
Voltage tolerances |
240 V to 480 V(1) |
Rated frequency |
50/60 Hz ± 10% |
Power factor/THDI |
> 0.99 / < 2.5% |
Output |
Rated voltage |
1ph + N: 230 V (can be configured 220/240 V)
3ph + N: 400 V (can be configured 380/415 V) |
Voltage tolerance |
static load ±1 % dynamic load in accordance with VFI-SS-111 |
Rated frequency |
50 / 60 Hz |
Frequency tolerance |
± 2% (configurable from 1% to 8%) |
Total output voltage distortion - linear load |
< 1 % |
Total output voltage distortion - non-linear load |
< 3% |
Overload |
125% for 10 minutes, 150% for 1 minute (1) |
Crest factor |
3:1 |
Bypass |
Rated voltage |
rated output voltage |
Voltage tolerance |
± 15% (configurable with from 10% to 20%) |
Rated frequency |
50 / 60 Hz |
Frequency tolerance |
± 2% |
Efficiency (TÜV SÜD verified) |
Online mode @ 50 % of load |
up to 96% |
Online mode @ 75 % of load |
up to 96% |
Online mode @ 100 % of load |
up to 96% |
ECO MODE |
up to 98% |
Environment |
Operating environment temperature |
from 0 °C up to +35 °C (from 15 °C to 25 °C for maximum battery life) |
Relative humidity |
0% - 95% without condensation |
Maximum altitude |
1000 m without derating (max. 3000 m) |
Acoustic level at 1 m (ISO 3746) |
< 52 dB |
< 55 dB |
< 60 dB (A) |
< 65 dB (A) |
UPS Cabinet |
Dimensions (W x D x H) [mm] |
444 x795 x800 |
444 x795 x1000 |
444 x 795 x 1400 |
600 x800 x1400 |
700x 800 x1930 |
Weight |
190 kg |
195 kg |
195 kg |
315 kg |
320 kg |
180 kg |
200 kg |
380
kg
|
460 kg |
Degree of protection |
IP 20 |
Colours |
RAL 7012 |
Standards |
Safety |
EN 62040-1 (TÜV SÜD certified), EN 60950-1 |
Performance |
EN62040-3 (VFI-SS-111) |
Electromagnetic compatibility (EMC) |
EN62040-2 |
Product declaration |
CE |