UPS SOCOMEC MASTERYS BC (8-12 kVA)

UPS SOCOMEC MASTERYS BC (8-12 kVA)

from 8 to 12 kVA

For critical IT and light industrial applications

The solution for

Light industrial applications

Servers

Telecommunications

Medical and laboratories

Advantages

The ideal protection

Simple and reliable power protection.

Tailored for medium-sized businesses.

Advantages of advanced technology.

An excellent size/power/back-up time ratio

Ideal for sensitive professional applications.

Suitable for protection in IT environments thanks to the internal back-up time and the possibility of installation in 19” rack cabinets.

Tailored to your environment

Easy to install.

Unique to the market with its highly compact size.

Flexible back-up times: different back-up time configurations are available either within the UPS standard cabinet or by using taller UPS cabinets, without changing the floor space (W = 444, D = 795 mm).

Increased system availability placing two UPS in parallel.

Combi Concept: BC108 and BC110 models are compatible with single or three-phase inputs, which can be configured during installation.

Fitted with a multilanguage LCD display.

Separate rectifier supply and bypass networks.

Standard and option features

Standard electrical features

Backfeed protection: detection circuit.

EBS (Expert Battery System) for battery management.

Electrical options

Dual input mains.

Internal maintanance bypass.

External maintanance bypass.

External battery cabinet.

Galvanic isolation transformer.

Parallel kit.

Standard communication features

MODBUS/JBUS RTU.

2 slots for communication options.

Communication options

Dry-contact interface.

Remote mimic panel.

MODBUS TCP.

PROFIBUS.

NET VISION: professional WEB/SNM interface for UPS monitoring and shutdown management of several operating systems

Technical Data

UPS and internal batteries


Sn [kVA] 8 10 12
Pn [kW] (0 °C ÷ 35 °C) 5.6 7 8.4
Input / output 1/1 • (1) • (1)  
Input / output 3/1 • (1) • (1)
Input / output 3/3  
Parallel configuration up to 2 units
Input
Rated voltage 230 V (1ph + N), 400 V (3ph + N)
Voltage tolerances ± 20 % (up to -35 % at 70 % nominal load)
Rated frequency  50/60 Hz ± 10%
Power factor / THDI 0.99 / < 6 % (2)
Output
Rated voltage 230 V (1ph + N), 400 V (3ph + N)
Voltage tolerance  ± 1 %
1ph + N can be configured 208 (3) /220/230/240 V
3ph + N can be configured 360 (3) /380/400/415 V
Rated frequency  50 / 60 Hz
Frequency tolerance ± 2 % (configurable from 1 % to 8 % with generating set)
Overload 125 % for 2 minutes, 150 % for 10 seconds
Crest factor 3:1 (complying with IEC 62040-3)
Power factor without derating up to 0.9 leading (up to 0.7 leading for 10 minutes) 
Bypass
Voltage tolerance 230 V (1ph + N), 400 V (3ph + N) ± 15 % (configurable from 10 % to 20 %)
Frequency tolerance 50/60 Hz ± 2 % (configurable from 1 % to 8 %)
Efficiency (TÜV SÜD verified)
Online mode @ 100 % of load up to 92 %
Eco Mode  up to 98 %
Environment
Operating ambient temperature from 0 °C up to +40 °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m (ISO 3746) < 50 dBA < 52 dBA
UPS cabinet  
Dimensions type S (short) W x D x H 444 x 795 x 800 mm
Dimensions type M (medium) W x D x H 444 x 795 x 1000 mm 
Dimensions type T (tall) W x D x H 444 x 795 x 1400 mm 
Weight with standard batteries 155 kg 160 kg 175 kg
Degree of protection IP20 (according to IEC 60529)
Colours RAL 7012, plastic front panels: dark grey
Standards
Safety EN 62040-1 (TÜV SÜD certified), EN 60950-1-1
Performance EN 62040-3 [VFI-SS-111]
EMC EN 62040-2
Product declaration CE