UPS SOCOMEC MASTERYS BC (8-12 kVA)
Standard and option features
Standard electrical features
Backfeed protection: detection circuit.
EBS (Expert Battery System) for battery management.
Electrical options
Dual input mains.
Internal maintanance bypass.
External maintanance bypass.
External battery cabinet.
Galvanic isolation transformer.
Parallel kit.
Standard communication features
MODBUS/JBUS RTU.
2 slots for communication options.
Communication options
Dry-contact interface.
Remote mimic panel.
MODBUS TCP.
PROFIBUS.
NET VISION: professional WEB/SNM interface for UPS monitoring and shutdown management of several operating systems
Technical Data
UPS and internal batteries
Sn [kVA] |
8 |
10 |
12 |
Pn [kW] (0 °C ÷ 35 °C) |
5.6 |
7 |
8.4 |
Input / output 1/1 |
• (1) |
• (1) |
|
Input / output 3/1 |
• (1) |
• (1) |
• |
Input / output 3/3 |
|
• |
• |
Parallel configuration |
up to 2 units |
Input |
Rated voltage |
230 V (1ph + N), 400 V (3ph + N) |
Voltage tolerances |
± 20 % (up to -35 % at 70 % nominal load) |
Rated frequency |
50/60 Hz ± 10% |
Power factor / THDI |
0.99 / < 6 % (2) |
Output |
Rated voltage |
230 V (1ph + N), 400 V (3ph + N) |
Voltage tolerance |
± 1 %
1ph + N can be configured 208 (3) /220/230/240 V
3ph + N can be configured 360 (3) /380/400/415 V |
Rated frequency |
50 / 60 Hz |
Frequency tolerance |
± 2 % (configurable from 1 % to 8 % with generating set) |
Overload |
125 % for 2 minutes, 150 % for 10 seconds |
Crest factor |
3:1 (complying with IEC 62040-3) |
Power factor without derating |
up to 0.9 leading (up to 0.7 leading for 10 minutes) |
Bypass |
Voltage tolerance |
230 V (1ph + N), 400 V (3ph + N) ± 15 % (configurable from 10 % to 20 %) |
Frequency tolerance |
50/60 Hz ± 2 % (configurable from 1 % to 8 %) |
Efficiency (TÜV SÜD verified) |
Online mode @ 100 % of load |
up to 92 % |
Eco Mode |
up to 98 % |
Environment |
Operating ambient temperature |
from 0 °C up to +40 °C (from 15 °C to 25 °C for maximum battery life) |
Relative humidity |
0% - 95% without condensation |
Maximum altitude |
1000 m without derating (max. 3000 m) |
Acoustic level at 1 m (ISO 3746) |
< 50 dBA |
< 52 dBA |
UPS cabinet |
Dimensions type S (short) W x D x H |
444 x 795 x 800 mm |
Dimensions type M (medium) W x D x H |
444 x 795 x 1000 mm |
Dimensions type T (tall) W x D x H |
444 x 795 x 1400 mm |
Weight with standard batteries |
155 kg |
160 kg |
175 kg |
Degree of protection |
IP20 (according to IEC 60529) |
Colours |
RAL 7012, plastic front panels: dark grey |
Standards |
Safety |
EN 62040-1 (TÜV SÜD certified), EN 60950-1-1 |
Performance |
EN 62040-3 [VFI-SS-111] |
EMC |
EN 62040-2 |
Product declaration |
CE |