UPS SOCOMEC DELPHYS MX

UPS SOCOMEC DELPHYS MX

from 250 to 900 kVA

the Mega Power protection up to 5.4 MVA

The solution for

Data centre

Industry

Telecommunications

Processes

Advantages

Lower Total Cost of Ownership

Minimized running costs, by:

very high efficiency of up to 93.5% (VFI mode),

Energy saver’ automatically adapts the number of running units to the real load,

free-cooling compatible.

Reduced footprint.

Exceptional high power density (the most compact unit of its class): 900 kVA in less than 3.2 meters (width) per unit including the bypass.

PFC “clean input” rectifier (without filters) with a lasting high input power factor whatever the operating conditions.

Intelligent built-in battery monitoring system interacts with “charging mode” to prolong battery lifetime.

Leading power factor load compatible without derating.

High reliability and availability

fault-tolerant architecture with internal redundancies and fan failure localisation.

Intelligent embedded battery monitoring with failed block localisation and preventative remote alarm.

Able to withstand an output short-circuit and overload.

Reliable and robust paralleling mode.

Multisystem automatic cross synchronisation (ACS) for an optimized use with STS.

Output isolation transformer to reduce the influence of N-GND (Neutral Line-to-Ground) voltage and load harmonic current on UPS inverter.

Flexible architecture

Parallel system with modular units.

Powerful central bypass for power extension or redundancy.

Tier 3 and Tier 4 compatible.

Designed for optimal use with STS in downstream network.

User-friendly operation

A control panel with graphic display for more ergonomic operation.

An array of “com-slot” plug-in communication interfaces, for upgrading your operating requirements.

Reduced MTTR thanks to extractible power bridges or fans on “cassette”.

Front accessibility for all components.

Simplified maintenance

Easy remote monitoring via web browser or via customer’s supervision systems (web, intranet, extranet…).

Very open connectivity (Modbus/Jbus, Jbustunnelling, LAN).

Parallel systems

  • To fulfil the most demanding needs for power supply availability, flexibility and the installation to be upgraded.
  • Modular parallel up to 6 units, development without constraint.
  • Double bypass, for easier operation.
  • Twin channel architecture with Static Transfer Systems.
Standard and option features

Standard electrical features

  • Slots for 7 communication cards.
  • Backfeed protection: detection circuit.
  • Standard interface:
  • 3 inputs (emergency stop, generating set, battery protection),
  • 4 outputs (general alarm, back-up, bypass, preventative maintenance needs).
  • EBS (Expert Battery System).
  • Parallel connection up to 6 units.

Electrical options

  • BHC Universal and BHC Interactive.
  • ACS synchronisation system.
  • Reinforced IP protection degree.
  • Ventilation filters.
  • Ventilation control.

Standard communication features

Multilanguage graphic display.

Communication options

  • GTS (Graphic Touch Screen).
  • Remote panel.
  • ADC interface (configurable voltage-free contacts).
  • RS232, RS422, RS485 serial port JBUS/MODBUS or PROFIBUS.
  • MODBUS TCP interface (JBUS/MODBUS tunneling).
  • NET VISION: professional WEB/SNMP interface for UPS monitoring and shutdown management of several operating systems.
  • Alarm notification via SMS.

Remote maintenance

LINK-UPS: maintenance software for continuous 24/7 monitoring of the SOCOMEC

Technical Data
Sn [kVA] 250 300 400 500 800 900
Pn [kW] 225 270 360 450 720 800
Input / output 3/3
Parallel configuration up to 6 units
Input
Rated input voltage (1) 380 V - 400 V - 415 V
Voltage tolerance 340 to 460 V 360 to 460 V
Rated input frequency 50/60 Hz
Frequency tolerance ± 5 Hz
Power factor / THDI 0.93 / < 4.5% 0.94 / < 5%
Output
Rated output voltage 380 V - 400 V - 415 V
Voltage tolerance < 1 % (static load), ± 2 % in 5 ms (dynamic load conditions from 0 to 100 %)
Nominal output frequency 50/60 Hz
Output frequency tolerance ± 0.2%
Total output voltage distortion - linear load < 2%
Total output voltage distortion - reference non-linear load (lEC 62043-3) < 4% < 3%
Short-circuit capability - 3.5 In 100 ms
Overload capabilìty 150% for 1 minute, 125% for 10 minutes
Crest factor 3:1
Output power factor without derating in kVA or kW 0.9 lagging to 0.9 leading
Bypass
Rated voltage 380 V - 400 V - 415 V
Voltage tolerance ± 10%
Rated frequency 50/60 Hz
Frequency tolerance ± 2 Hz (0.2 Hz to 4 Hz settable)
Efficiency
Online mode up to 93.5%
ECO-MODE 98%
Environment
Operating ambient temperature from 0 °C up to +35 °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0 % - 95 % without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m (ISO 3746) (2) < 70 dBA < 72 dBA < 75 dbA
UPS Cabinet
Dimensions (W x D x H) 1600 x 995 x 1930 mm 3200 x 995 x 2210 mm
Weight 2500 kg 2800 kg 3300 kg 5900 kg
Degree of protection IP20
Colours RAL 9006
Standards
Safety IEC 62040-1; EN 62040-1; IEC 60950-1
EMC IEC 62040-2; EN 62040-2
Performance and test IEC 62040-3
Product comformity CE

(1) Delphys MX 250-500: three-phase 220-230-240 V on demand.

(2) As per power range.