UPS SOCOMEC DELPHYS MP Elite

UPS SOCOMEC DELPHYS MP Elite

from 80 to 200 kVA

Your protection up to 1 200 kVA

The solution for

  • Data centres
  • Industry
  • Telecommunications
  • Processes

Advantages

High quality power supply

The SVM digital modulation (Space Vector Modulation) fitted to the transformer integrated downstream of the inverter allows supply to your installations with:

precise voltage even when the load between phases is completely unbalanced,

stable output voltage during significant and quick variations in loads (± 2% in less than 5 ms).

Active power without derating, for loads with a lagging power factor and up to 0.9 leading.

Sinusoidal THDV output voltage < 2 % with linear loads and < 3 % with non-linear loads.

With sinusoidal voltage for non-linear loads (Crest Factor 3:1).

A very high short-circuit capacity which facilitates the selection of protective devices for selectivity in the downstream distribution.

An isolation transformer is installed on the inverter output to ensure complete galvanic isolation between DC circuit and load output. This insulation also provides a separation between the two inputs when they are supplied by different sources.

High availability

A fault-tolerant architecture with redundancy of basic functions, such as the ventilation system.

The ideal solution for grouping with generator sets without using an excessively large generator.

A variety of architectures for parallel operations, to deal with redundancy, management and changes in power output.

Battery availability at all times

An innovative load algorithm which adapts to the environmental conditions and the condition of the battery to increase its life.

A highly-developed monitoring system, capable of locating and correcting any problems interacting with the charging device.

Cost-effective equipment

A “clean” IGBT rectifier. The power factor and THDI at the rectifier input are constant whatever the battery charge status (continuous voltage level) and the load rate of the UPS. It eliminates any disturbance on the upstream network (transformer, generator set and distribution).

The cutting rectifier guarantees the supply of current with an exceptionally low rate of harmonic distortion: THDI < 2.5%.

Reduced current consumption due to an input power factor of 0.99 without derating, and constant in every situation.

User-friendly operation

A control panel with graphic display for more ergonomic operation.

An array of “com-slot” plug-in communication interfaces, for upgrading your operating requirements evolution.

Simplified maintenance

An advanced diagnostic system.

A remote access device connected to the remote maintenance centre.

Easy access to subassemblies and components, facilitating tests and reducing maintenance time (MTTR).

Standard and option features

Parallel systems

Modular parallel up to 6 units, development without constraint.

Distributed or centralized bypass, progressive development.

Twin-channel architecture with Static Transfer Systems.

Standard electrical features

Slots for 7 communication cards.

Backfeed protection: detection circuit

Standard interface:

3 inputs (emergency stop, generating set, battery protection),

4 outputs (general alarm, back-up, bypass, preventative maintenance needs).

Parallel connection up to 6 units.

Electrical options

BHC Universal.

EBS (Expert Battery System).

Flywheel compatible.

ACS synchronisation system.

Reinforced IP protection degree.

Ventilation filters.

Ventilation failure detection

Top entry connection

Standard communication features

Multilanguage graphic display.

Embedded dry contacts.

Communication options

  • GTS (Graphic Touch Screen).
  • Remote panel.
  • ADC interface (configurable voltage-free contacts).
  • RS232, RS422, RS485 serial port JBUS/MODBUS or PROFIBUS.
  • MODBUS TCP interface (JBUS/MODBUS tunneling).
  • NET VISION: professional WEB/SNMP interface for UPS monitoring and shutdown management of several operating systems.

Remote maintenance

LINK-UPS: maintenance software for continuous 24/7 monitoring of the SOCOMEC.

Technical Data
Sn [kVA] 80 100 120 160 200
Pn [kW] 64 80 96 128 160
Input / output 3/3
Parallel configuration up to 6 units (distributed or centralised bypass)
Input
Rated voltage

380 V - 400 V - 415 V(1)

Voltage tolerances

340 to 460 V

Rated frequency 50/60 Hz
Frequency tolerance 45 to 65 Hz
Power factor / THDI 0.99 constant / 2.5 % without filter
Output
Rated voltage 380 V - 400 V - 415 V (configurable) (1)
Voltage tolerance < 1 % (static load), ± 2 % in 5 ms (dynamic load conditions from 0 to 100 %)
Rated frequency 50/60 Hz
Frequency tolerance ± 0.2%
Total output voltage distortion - linear load < 2%
Total output voltage distortion - non-linear load < 4%
Short-circuit current Up to 3.5 In
Overload 150 % for 1 minute, 125 % for 10 minutes
Crest factor  3:1
Power factor without derating 0.9 lagging to 0.9 leading
Bypass
Rated voltage 380 V - 400 V - 415 V
Voltage tolerance ± 10% (selectable)
Rated frequency 50/60 Hz
Frequency tolerance ± 2%
Efficiency (TÜV SÜD verified)
Online mode 94%
Eco Mode 98%
Environment
Operating ambient temperature from 0 °C up to +35 °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000 m without de-rating (3000 m max)
Acoustic level at 1 m
(ISO 3746)
65 dBA 67dBA
UPS cabinet 
Dimensions (W x D x H) [mm] 1000 x 800 x 1930 mm
Weight (2) 740 kg 860 kg 1020 kg
Degree of protection IP20 (other IP as option)
Colours RAL 9006
Standards
Safety IEC 62040-1-2, IEC 60950
Performance IEC 62040-3
EMC IEC 62040-2
Product declaration CE