UPS SOCOMEC DELPHYS GP - Green Power 2.0 range

UPS SOCOMEC DELPHYS GP - Green Power 2.0 range

from 160 to 800 kVA/kW

Ultra high energy efficiency and maximum power

availability up to 4 MW

The solution for

Data centres

Telecommunications

Service sector

IT Networks/ Infrastructures

Advantages

Energy Saving: high efficiency without compromise

Offers the highest efficiency in the market using VFI – Double Conversion Mode, the only UPS working-mode that assures total load protection against all mains quality problems.

Ultra high efficiency output independently tested and verified by an international certification organization in a wide range of load and voltage operating condition.

Ultra high efficiency in VFI mode is provided by an innovative topology (3-Level technology) that has been developed for all the Green Power UPS ranges.

Full-rated power: kW=kVA

No power downgrading when supplying the latest generation of servers (leading or unity power factor).

Real full power, according to IEC 62040: kW=kVA (unity power factor design) means 25% more active power available compared to legacy UPS.

Suitable also for leading power factor loads down to 0.9 without apparent derating.

Significant cost savings (TCO)

Maximum energy saving thanks to 96% efficiency in true double conversion mode: 50% saving on energy losses compared to legacy UPS gives significant savings in energy bill.

Up to 99% efficiency with FAST ECOMODE

UPS “self-paying” with energy saving.

Energy Saver mode for global efficiency improvement on parallel systems.

kW=kVA means maximum power available with the same UPS rating: no overdesign cost and therefore less €/kW.

Upstream infrastructure cost optimization (sources and distribution), thanks to high performance IGBT rectifier.

Extended battery life and performance:

Long life battery,

Long life battery,

EBS (Expert Battery System) charging management improves battery service life

BHC INTERACTIVE: Accurate battery monitoring with UPS interactivity for even more prolonged service life

Standard and option features

Parallel systems

To fulfil the most demanding needs for power supply availability, flexibility and the installation to be upgraded.

Modular parallel configurations up to 4 MW, development without constraint.

Distributed or centralized bypass flexibility to ensure a perfect compatibility with the electrical infrastructure.

Twin channel architecture with Static Transfer Systems.

Distributed or shared battery for energy storage optimization on parallel systems.

Standard electrical features

Dual input mains.

Integrated maintenance bypass.

Backfeed protection: detection circuit.

EBS (Expert Battery System) for battery management.

Redundant cooling.

Battery temperature sensor.

Electrical options

External maintanance bypass.

Extended battery charger capability.

Shared battery.

Flywheel compatible.

Galvanic isolation transformer.

Backfeed isolation device.

ACS synchronisation system.

BHC Interactive.

Fast EcoMode.

Standard communication features

User-friendly multilingual interface with graphic display.

2 slots for communication options.

RS232 serial port for modem.

Ethernet connection (WEB/SNMP/MODBUS TCP/email).

USB port for event log access.

Communication options

Advanced server shutdown options for stand-alone and virtual servers.

4 additional slots for communication options.

ADC interface (configurable voltage-free contacts).

MODBUS/JBUS RTU.

BACnet/IP interface

SMS alert.

Remote monitoring service

LINK-UPS, remote monitoring service that connects your UPS to your Critical Power specialist 24 / 7.

Technical Data
Sn (kVA) 160 200 250 320 400 500 600 800
Pn [kW] 160 200 250 320 400 500 600 500
Input / output 3/3
Parallel configuration up to 4 MW
Input
Rated voltage 400V 3ph
Voltage tolerances 200 V to 480 V (1)
Rated frequency 50 / 60 Hz
Frequency tolerance ± 10 Hz
Power factor/THDI > 0.99 / < 2.5%(2)
Output
Rated voltage 3ph + N 400 V
Voltage tolerance static load  static load ±1% dynamic load in accordance with VFI-SS-111
Rated frequency 50 / 60 Hz
Frequency tolerance ± 2% (configurable for GenSet compatibility)
Total output voltage distortion - linear load ThdU < 1.5%
Total output voltage distortion - non-linear load (lEC 62043-3) ThdU < 3%
Short circuit current up to 3.4 x In
Overload 125% for 10 minutes, 150% for 1 minute (1)
Crest factor 3:1
Bypass
Rated voltage rated output voltage
Voltage tolerance ± 15% (configurable with from 10% to 20%)
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable for GenSet compatibility)
Efficiency
Online mode @ 40 % of load up to 96%
Online mode @ 75 % of load up to 96%
Online mode @ 100 % of load up to 96%
Fast EcoMode up to 99%
Environment
Operating ambient temperature from 10 °C up to +40 °C (1) (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000 m without declassing (max. 3000 m)
Acoustic level at 1 m (ISO 3746) <65 dBA <67 dBA <70 dBA <68 dBA <70 dBA <72 dBA <74 dBA
UPS Cabinet
Dimensions (W x D x H) 700 x 800 x 1930 mm 1000x 950x 1930 mm 1400 x 800 x 1930 mm 1600x 950x 1930 mm

3700 x 950 x 2055 mm

Weight 470 kg 490 kg 850 kg 980 kg 1000 kg 1500 kg 3400 kg
Degree of protection IP 20 (other IP as option)
Colours cabinet: RAL 7012, door: silver grey
Standards
Safety EN 62040-1, EN 60950-1
EMC EN62040-2
Performance EN62040-3 (VFI-SS-111)
Product declaration CE

(1) Conditions apply.

(2) With input THDV < 1%